This example shows how to design and tune a gain-scheduled controller for a chemical reactor transitioning from low to high conversion rate. For background, see Seborg, D.E. et al., "Process Dynamics and Control", 2nd Ed., 2004, Wiley, pp. 34-36.
The process considered here is a continuous stirred tank reactor (CSTR) during transition from low to high conversion rate (high to low residual concentration). Because the chemical reaction is exothermic (produces heat), the reactor temperature must be controlled to prevent a thermal runaway. The control task is complicated by the fact that the process dynamics are nonlinear and transition from stable to unstable and back to stable as the conversion rate increases. The reactor dynamics are modeled in Simulink. The controlled variables are the residual concentrationCr
和the reactor temperatureTr
, and the manipulated variable is the temperatureTc
of the coolant circulating in the reactor's cooling jacket.
open_system('rct_CSTR_OL')
We want to transition from a residual concentration of 8.57 kmol/m^3 initially down to 2 kmol/m^3. To understand how the process dynamics evolve with the residual concentrationCr
, find the equilibrium conditions for five values ofCr
between 8.57 and 2 and linearize the process dynamics around each equilibrium. Log the reactor and coolant temperatures at each equilibrium point.
CrEQ = linspace(8.57,2,5)';% concentrationsTrEQ = zeros(5,1);% reactor temperaturesTcEQ = zeros(5,1);% coolant temperatures% Specify trim conditionsopspec = operspec('rct_CSTR_OL',5);fork=1:5% Set desired residual concentrationopspec(k).Outputs(1).y = CrEQ(k); opspec(k).Outputs(1).Known = true;end% Compute equilibrium condition and log corresponding temperatures[op,report] = findop('rct_CSTR_OL',opspec,...findopOptions('DisplayReport','off'));fork=1:5 TrEQ(k) = report(k).Outputs(2).y; TcEQ(k) = op(k).Inputs.u;end% Linearize process dynamics at trim conditionsG = linearize('rct_CSTR_OL','rct_CSTR_OL/CSTR', op); G.InputName = {'Cf','Tf','Tc'}; G.OutputName = {'Cr','Tr'};
Plot the reactor and coolant temperatures at equilibrium as a function of concentration.
subplot(311), plot(CrEQ,'b-*'), grid, title('Residual concentration'), ylabel('CrEQ') subplot(312), plot(TrEQ,'b-*'), grid, title('Reactor temperature'), ylabel('TrEQ') subplot(313), plot(TcEQ,'b-*'), grid, title('Coolant temperature'), ylabel('TcEQ')
An open-loop control strategy consists of following the coolant temperature profile above to smoothly transition between theCr
=8.57 andCr
=2 equilibria. However, this strategy is doomed by the fact that the reaction is unstable in the mid range and must be properly cooled to avoid thermal runaway. This is confirmed by inspecting the poles of the linearized models for the five equilibrium points considered above (three out of the five models are unstable).
pole(G)
ans(:,:,1) = -0.5225 + 0.0000i -0.8952 + 0.0000i ans(:,:,2) = 0.1733 + 0.0000i -0.8866 + 0.0000i ans(:,:,3) = 0.5114 + 0.0000i -0.8229 + 0.0000i ans(:,:,4) = 0.0453 + 0.0000i -0.4991 + 0.0000i ans(:,:,5) = -1.1077 + 1.0901i -1.1077 - 1.0901i
The Bode plot further highlights the significant variations in plant dynamics while transitioning fromCr
=8.57 toCr
=2.
clf, bode(G(:,'Tc'),{0.01,10})
To prevent thermal runaway while ramping down the residual concentration, use feedback control to adjust the coolant temperatureTc
based on measurements of the residual concentrationCr
和reactor temperatureTr
. For this application, we use a cascade control architecture where the inner loop regulates the reactor temperature and the outer loop tracks the concentration setpoint. Both feedback loops are digital with a sampling period of 0.5 minutes.
open_system('rct_CSTR')
The target concentrationCref
ramps down from 8.57 kmol/m^3 at t=10 to 2 kmol/m^3 at t=36 (the transition lasts 26 minutes). The corresponding profileTref
for the reactor temperature is obtained by interpolating the equilibrium valuesTrEQ
从分析。的控制er computes the coolant temperature adjustmentdTc
relative to the initial equilibrium valueTcEQ(1)
=297.98 forCr
=8.57. Note that the model is set up so that initially, the outputTrSP
of the "Concentration controller" block matches the reactor temperature, the adjustmentdTc
is zero, and the coolant temperatureTc
在其平衡值吗TcEQ(1)
.
clf t = [0 10:36 45]; C = interp1([0 10 36 45],[8.57 8.57 2 2],t); subplot(211), plot(t,C), grid, set(gca,'ylim',[0 10]) title('Target residual concentration'), ylabel('Cref') subplot(212), plot(t,interp1(CrEQ,TrEQ,C)) title('Corresponding reactor temperature at equilibrium'), ylabel('Tref'), grid
UseTuningGoal
objects to capture the design requirements. First,Cr
should follow setpointsCref
with a response time of about 5 minutes.
R1 = TuningGoal.Tracking('Cref','Cr',5);
The inner loop (temperature) should stabilize the reaction dynamics with sufficient damping and fast enough decay.
MinDecay = 0.2; MinDamping = 0.5;% Constrain closed-loop poles of inner loop with the outer loop openR2 = TuningGoal.Poles('Tc',MinDecay,MinDamping); R2.Openings ='TrSP';
The Rate Limit block at the controller output specifies that the coolant temperatureTc
cannot vary faster than 10 degrees per minute. This is a severe limitation on the controller authority which, when ignored, can lead to poor performance or instability. To take this rate limit into account, observe thatCref
varies at a rate of 0.25 kmol/m^3/min. To ensure thatTc
does not vary faster than 10 degrees/min, the gain fromCref
toTc
should be less than 10/0.25=40.
R3 = TuningGoal.Gain('Cref','Tc',40);
Finally, require at least 7 dB of gain margin and 45 degrees of phase margin at the plant inputTc
.
R4 = TuningGoal.Margins('Tc',7,45);
To achieve these requirements, we use a PI controller in the outer loop and a lead compensator in the inner loop. Due to the slow sampling rate, the lead compensator is needed to adequately stabilize the chemical reaction at the mid-range concentrationCr
= 5.28 kmol/m^3/min. Because the reaction dynamics vary substantially with concentration, we further schedule the controller gains as a function of concentration. This is modeled in Simulink using Lookup Table blocks as shown in Figures 1 and 2.
Figure 1: Gain-scheduled PI controller for concentration loop.
Figure 2: Gain-scheduled lead compensator for temperature loop.
Tuning this gain-scheduled controller amounts to tuning the look-up table data over a range of concentration values. Rather than tuning individual look-up table entries, parameterize the controller gainsKp,Ki,Kt,a,b
as quadratic polynomials inCr
, for example,
Besides reducing the number of variables to tune, this approach ensures smooth gain transitions asCr
varies. Usingsystune
, you can automatically tune the coefficientsto meet the requirementsR1-R4
at the five equilibrium points computed above. This amounts to tuning the gain-scheduled controller at five design points along theCref
trajectory. Use thetunableSurface
object to parameterize each gain as a quadratic function ofCr
. The "tuning grid" is set to the five concentrationsCrEQ
和the basis functions for the quadratic parameterization are. Most gains are initialized to be identically zero.
TuningGrid = struct('Cr',CrEQ); ShapeFcn = @(Cr) [Cr , Cr^2]; Kp = tunableSurface('Kp', 0, TuningGrid, ShapeFcn); Ki = tunableSurface('Ki', -2, TuningGrid, ShapeFcn); Kt = tunableSurface('Kt', 0, TuningGrid, ShapeFcn); a = tunableSurface('a', 0, TuningGrid, ShapeFcn); b = tunableSurface('b', 0, TuningGrid, ShapeFcn);
Because the target bandwidth is within a decade of the Nyquist frequency, it is easier to tune the controller directly in the discrete domain. Discretize the linearized process dynamics with sample time of 0.5 minutes. Use the ZOH method to reflect how the digital controller interacts with the continuous-time plant.
Ts = 0.5; Gd = c2d(G,Ts);
Create anslTuner
interface for tuning the quadratic gain schedules introduced above. Use block substitution to replace the nonlinear plant model by the five discretized linear modelsGd
obtained at the design pointsCrEQ
. UsesetBlockParam
to associate the tunable gain functionsKp
,Ki
,Kt
,a
,b
with the Lookup Table blocks of the same name.
BlockSubs = struct('Name','rct_CSTR/CSTR','Value',Gd); ST0 = slTuner('rct_CSTR',{'Kp','Ki','Kt','a','b'},BlockSubs); ST0.Ts = Ts;% sample time for tuning% Register points of interestST0.addPoint({'Cref','Cr','Tr','TrSP','Tc'})% Parameterize look-up table blocksST0.setBlockParam('Kp',Kp); ST0.setBlockParam('Ki',Ki); ST0.setBlockParam('Kt',Kt); ST0.setBlockParam('a',a); ST0.setBlockParam('b',b);
You can now usesystune
to tune the controller coefficients against the requirementsR1-R4
. Make the stability margin requirement a hard constraints and optimize the remaining requirements.
ST = systune(ST0,[R1 R2 R3],R4);
Final: Soft = 1.23, Hard = 0.99989, Iterations = 197
The resulting design satisfies the hard constraint (Hard<1
) and nearly satisfies the remaining requirements (Soft
close to 1). To validate this design, simulate the responses to a ramp in concentration with the same slope asCref
. Each plot shows the linear responses at the five design pointsCrEQ
.
t = 0:Ts:20; uC = interp1([0 2 5 20],(-0.25)*[0 0 3 3],t); subplot(211), lsim(getIOTransfer(ST,'Cref','Cr'),uC) grid, set(gca,'ylim',[-1.5 0.5]), title('Residual concentration') subplot(212), lsim(getIOTransfer(ST,'Cref','Tc'),uC) grid, title('Coolant temperature variation')
Note that rate of change of the coolant temperature remains within the physical limits (10 degrees per minute or 5 degrees per sample period).
Inspect how each gain varies withCr
during the transition.
% Access tuned gain schedulesTGS = getBlockParam(ST);% Plot gain profilesclf subplot(321), viewSurf(TGS.Kp), ylabel('Kp') subplot(322), viewSurf(TGS.Ki), ylabel('Ki') subplot(323), viewSurf(TGS.Kt), ylabel('Kt') subplot(324), viewSurf(TGS.a), ylabel('a') subplot(325), viewSurf(TGS.b), ylabel('b')
To validate the gain-scheduled controller in Simulink, first usewriteBlockValue
to apply the tuning results to the Simulink model. For each Lookup Table block, this evaluates the corresponding quadratic gain formula at the table breakpoints and updates the table data accordingly.
writeBlockValue(ST)
Next push the Play button to simulate the response with the tuned gain schedules. The simulation results appear in Figure 3. The gain-scheduled controller successfully drives the reaction through the transition with adequate response time and no saturation of the rate limits (controller outputdu
matches effective temperature variationdTc
). The reactor temperature stays close to its equilibrium valueTref
, indicating that the controller keeps the reaction near equilibrium while preventing thermal runaway.
Figure 3: Transition with gain-scheduled cascade controller.
Alternatively, you can tune the gain schedules directly in MATLAB without using theslTuner
interface. First parameterize the gains as quadratic functions ofCr
as done above.
TuningGrid = struct('Cr',CrEQ); ShapeFcn = @(Cr) [Cr , Cr^2]; Kp = tunableSurface('Kp', 0, TuningGrid, ShapeFcn); Ki = tunableSurface('Ki', -2, TuningGrid, ShapeFcn); Kt = tunableSurface('Kt', 0, TuningGrid, ShapeFcn); a = tunableSurface('a', 0, TuningGrid, ShapeFcn); b = tunableSurface('b', 0, TuningGrid, ShapeFcn);
Use these gains to build the PI and lead controllers.
PI = pid(Kp,Ki,'Ts',Ts,'TimeUnit','min'); PI.u ='ECr'; PI.y ='TrSP'; LEAD = Kt * tf([1 -a],[1 -b],Ts,'TimeUnit','min'); LEAD.u ='ETr'; LEAD.y ='Tc';
Useconnect
to build a closed-loop model of the overall control system at the five design points. Mark the controller outputsTrSP
和Tc
as "analysis points" so that loops can be opened and stability margins evaluated at these locations. The closed-loop modelT0
is a 5-by-1 array of linear models depending on the tunable coefficients ofKp,Ki,Kt,a,b
. Each model is discrete and sampled every half minute.
Gd.TimeUnit ='min'; S1 = sumblk('ECr = Cref - Cr'); S2 = sumblk('ETr = TrSP - Tr'); T0 = connect(Gd(:,'Tc'),LEAD,PI,S1,S2,'Cref','Cr',{'TrSP','Tc'});
Finally, usesystune
to tune the gain schedule coefficients.
T = systune(T0,[R1 R2 R3],R4);
Final: Soft = 1.23, Hard = 0.99987, Iterations = 193
The result is similar to the one obtained above. Confirm by plotting the gains as a function ofCr
using the tuned coefficients inT
.
clf subplot(321), viewSurf(setBlockValue(Kp,T)), ylabel('Kp') subplot(322), viewSurf(setBlockValue(Ki,T)), ylabel('Ki') subplot(323), viewSurf(setBlockValue(Kt,T)), ylabel('Kt') subplot(324), viewSurf(setBlockValue(a,T)), ylabel('a') subplot(325), viewSurf(setBlockValue(b,T)), ylabel('b')
You can further validate the design by simulating the linear responses at each design point. However, you need to return to Simulink to simulate the nonlinear response of the gain-scheduled controller.
setBlockParam
|slTuner